Different protective relays are used for different power system equipment
protection
Now let’s have a look on which
different protective relays are used in different power system equipment
protection schemes
Relays
for Transmission & Distribution Lines protection
SL
|
Lines
to be protected
|
Relays
to be used
|
1
|
400 KV
Transmission Line |
Main-I: Non switched or Numerical
Distance Scheme
Main-II: Non switched or Numerical Distance Scheme |
2
|
220 KV
Transmission Line |
Main-I: Non switched distance
scheme (Fed from Bus PTs)
Main-II: Switched distance scheme (Fed from line CVTs) With a changeover facility from bus PT to line CVT and vice-versa. |
3
|
132 KV
Transmission Line |
Main Protection: Switched distance
scheme (fed from bus PT)
Backup Protection: 3 Nos. directional IDMT O/L Relays and 1 No. Directional IDMT E/L relay. |
4
|
33 KV lines
|
Non-directional IDMT 3 O/L and 1
E/L relays.
|
5
|
11 KV lines
|
Non-directional IDMT 2 O/L and 1
E/L relays.
|
Relays
for Transformer protection
SL
|
Voltage
Ratio and
Capacity of Transformer |
Relays
on HV Side
|
Relays
on LV Side
|
Common
Relays |
1
|
11/132 KV
Generator Transformer |
3 nos Non-Directional O/L Relay
1 no Non-Directional E/L Relay and/or standby E/F + REF Relay |
– -
|
Differential Relay or
Overall differential Relay Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
2
|
13.8/220 KV
15.75/220 KV 18/400 KV 21/400 KV Generator Transformer |
3 nos Non-Directional O/L Relay
1 no Non-Directional E/L Relay and/or standby E/F + REF Relay |
– -
|
Differential Relay or
Overall differential Relay Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
3
|
220 /6.6KV
Station Transformer |
3 nos Non-Directional O/L Relay
1 no Non-Directional E/L Relay and/or standby E/F + REF Relay |
3 nos Non-Directional O/L Relay
|
Differential Relay
Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
4
|
Gen-volt/6.6KV UAT
|
3 nos Non-Directional O/L Relay
|
3 nos Non-Directional O/L Relay
|
Differential Relay
Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
5
|
132/33/11KV upto 8 MVA
|
3 nos O/L Relay
1 no E/L Relay |
2 nos O/L Relays
1 no E/L Relay |
Buchholz Relay
OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
6
|
132/33/11KV above 8 MVA &
below 31.5 MVA |
3 nos O/L Relay
1 no Directional E/L Relay |
3 nos O/L Relay
1 no E/L Relay |
Differential Relay
Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
7
|
132/33KV, 31.5 MVA & above
|
3 nos O/L Relay
1 no Directional E/L Relay |
3 nos O/L Relay
1 no E/L Relay |
Differential Relay
Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
8
|
220/33 KV, 31.5MVA &
50MVA 220/132KV, 100 MVA |
3 nos O/L Relay
1 no Directional E/L Relay |
3 nos O/L Relay
1 no Directional E/L Relay |
Differential Relay
Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay |
9
|
400/220KV 315MVA
|
3 nos Directional O/L Relay
(with dir.highset) 1 no Directional E/L relay. Restricted E/F relay 3 nos Directional O/L Relay for action |
3 nos Directional O/L Relay
(with dir.highset) 1 no Directional E/L relay. Restricted E/F relay |
Differential Relay
Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay Over Load (Alarm) Relay |
Points to be remembered in respect
of protection of transformers
i. No Buchholz relay for
transformers below 500 KVA capacity
ii. Transformers up to 1500 KVA shall have only Horn gap protection
iii. Transformers above 1500 KVA and upto 8000 KVA of 33/11KV ratio shall have one group control breaker on HV side and individual LV breakers if there is more than one transformer.
iv. Transformers above 8000 KVA shall have individual HV and LV circuit breakers.
v. The relays indicate above shall be provided on HV and LV
vi. LAs to be provided on HV & LV for transformers of all capacities and voltage class.
vii. OLTC out of step protection is to be provided where Master follower scheme is in operation
viii. Fans failure and pumps failure alarms to be connected.
ix. Alarms for O.T., W.T., Buchholz (Main tank & OLTC) should be connected.
ii. Transformers up to 1500 KVA shall have only Horn gap protection
iii. Transformers above 1500 KVA and upto 8000 KVA of 33/11KV ratio shall have one group control breaker on HV side and individual LV breakers if there is more than one transformer.
iv. Transformers above 8000 KVA shall have individual HV and LV circuit breakers.
v. The relays indicate above shall be provided on HV and LV
vi. LAs to be provided on HV & LV for transformers of all capacities and voltage class.
vii. OLTC out of step protection is to be provided where Master follower scheme is in operation
viii. Fans failure and pumps failure alarms to be connected.
ix. Alarms for O.T., W.T., Buchholz (Main tank & OLTC) should be connected.